Contact info Contact info Contact info E-mail to
AFS manual

 

Eagle Christian Church

AdvanTex Treatment and Drip Disposal Solves Nitrogen Issues

cover the entire width of the property to insure complete mixing across the site’s groundwater migration path.

 

Conventional treatment and drainfield systems would not provide an acceptable solution to the nitrogen or drainfield coverage problems, and after much discussion, R.C. Worst & Co., Inc. proposed a solution that included Orenco Systems’ AdvanTex® treatment system coupled with Geoflow drip disposal technology.  The treatment system was configured to deal with huge peak flows typical of a church facility while providing the environment necessary to maximize biological nitrogen removal.  The drip system allowed us to place the entire drainfield over a long, narrow strip of property while introducing the treated waste very shallow into the soil. 

 

Once installed, and the necessary adjustments were made, the system appears to be operating without a hitch.  Using Orenco’s TeleComm control panel technology, church staff and operation & maintenance provider receive alert and alarm condition via e-mail with the option to access the panel remotely from an available Internet connection.

 

The Eagle Christian Church design team came to R.C. Worst & Co., Inc. with a problem.  The congregation had out grown their current building. The church needed a larger sanctuary and additional areas to support their current rate of growth.  A major problem arose when the subject of wastewater treatment and disposal was broached. Due to high nitrate readings in the area’s groundwater, Idaho Department of Environmental Quality required an additional study to determine the proposed expansion’s nitrogen impact at the site. 

 

The findings of the study revealed an interesting problem.  To satisfy regulatory requirements, total nitrogen discharge would be limited to 20 mg/L or less, and the drainfield design would be such to

Project Summary

Installation Date

January 2008

 

Description

Advantex® Treatment System with Pressurized Drip Drainfield

 

Design Flow

1,200 gpd

System Engineer

Don George, P.E.

 

Contractor

Petra

 

Installer

Master Excavation

 

 

Operator

Master Excavation

 

System Summary

Treatment System

  • 8,000 Gallon Xerxes fiberglass primary tank
  • 10,000 Gallon Xerxes fiberglass mitigation Tank
  • 3,000 Gallon Xerxes Fiberglass Denite/Recirculation Chamber
  • 5,000 Gallon Xerxes Recirculation Tank
  • 1,500 Gallon Distribution/dose Tank
  • 3 – AdvanTex AX20 Treatment Pods

 

Disposal System:

  • 2 - 1500 Gallon Drip Drainfield Dose Tanks
  • 4 Zone Time Doses Drip Drainfield
  • Geoflow Pressure Compensating Emitter Drip Tubing installed shallow across baseball field on site

 

Performance Summary

Operation & Maintenance

Maintenance of tanks, pumps, AdvanTex Treatment System and Drip Drainfield – Avg. 20 hours per year

 

Maintenance Costs

Yearly Sampling and Inspections = $275 per visit

 

 

Performance

 

 

Permit Limits

Acutal Test

06/14/2009

BOD5

TSS

TN

30 mg/L

30 mg/L

20 mg/L

10 mg/L

>3 mg/L

17 mg/L