Littelfuse 201-100-SP Voltage Monitor Specifications
Line Voltage . . . . . . . . . . . . 95 to 120 VAC
Frequency
. . . . . . . . . . . . . . . . . . . . . 50 or 60 Hz
Low Voltage (% of set point)
- Trip . . . . . . . . . . . . . . . . . . . . . . . . . . 90%
- Reset . . . . . . . . . . . . . . . . . . . . . . . . . 93%
Trip Delay Time
- High/Low Voltage Fault. . . . . . . . . . . . . . . . 4 seconds
Restart Delay Time
- After a Fault . . . . . . . . . . . . . . . . . 2 seconds
- After a Complete Power Loss. . . . . . . 2 seconds
Output Contact Rating (SPDT)
- Pilot Duty . . . . . . . . . . . . . . . . . . . . . . . . 480 VA @ 240
VAC
- General Purpose . . . . . . . . . . . . . . . . . . . . . . . or 10A @240
VAC
Temperature Range
- Operating . . . . . . . . . . . . . . . . . -20° to 70°C (-4° to 158°F)
- Storage . . . . . . . . . . . . . . . . . . -40° to 80°C (-40° to 176°F)
Maximum Input Power . . . . . . . . . . . . . 5 Watts
Transient Protection(Internal) . . . . . . 2500V for 10 ms
Safety Marks
- UL (OT08PC Octal Socket Required) . . . . . . .UL508 (File #E68520)
- CE . . . . . . . . . . . IEC 60947-6-2
Weight . . . . . . . . . . . . . . . . . . . . . . . . 12.8 oz.
Mounting Method
. . . . . . . . . . . DIN Rail or Surface Mount (plug in to OT08PC socket)
Socket Available
. . . . . . . . . . . Model OT08PC (UL Rated 600V)
The 600V socket can be surface mounted or installed on DIN Rail.
WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov